Skip to the drawing
Built, Mapped & Planted Streets, structures and street plans — and the problems they answer.

Diagram deep-dive

How Does a Sewer System Work? Sometimes Rain Shares the Pipe

The problem wastewater leaves buildings day and night and has to reach a treatment plant, preferably by running downhill on its own.

Built, Mapped & Planted Issued

TL;DR

A sewer system moves wastewater downhill through gravity sewers laid on a slope; the 2014 Ten States Standards recommend at least 0.40 ft of fall per 100 ft for an 8-inch pipe. Where the ground rises, a pumping station lifts the flow into a pressure pipe that empties into the next gravity sewer, on the way to a treatment plant.

Title block
NameSewer system: gravity sewers, lift stations, combined and separate pipes
CategoryUnder the Street
Where it appearsUnder streets, seen from the curb as inlets, grates and manhole covers
Original problemCarry wastewater, and in combined systems rainwater too, from buildings and streets to a treatment plant
Key dimensions or parametersIn the 2014 Ten States Standards: smallest public gravity sewer for raw wastewater 8 in (200 mm); recommended minimum slope for it 0.40 ft per 100 ft
SourcesTen States Standards (2014 edition); EPA, Combined Sewer Overflow Basics (updated September 24, 2026)

This block as data (CSV) where this data comes from

Data: U.S. Environmental Protection Agency (EPA), Combined Sewer Overflow Basics (updated 2026-09-24), retrieved 2026-11-18; Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

Schematic street section of a combined sewer, where building drains and the curb inlet feed one pipe

Model schematic layout, not any city

Open the drawing full size

"Street section, combined sewer system (schematic)" by Built, Mapped & Planted, https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/ — CC BY 4.0, https://creativecommons.org/licenses/by/4.0/

Data: U.S. Environmental Protection Agency (EPA), Combined Sewer Overflow Basics (updated 2026-09-24), retrieved 2026-11-18; Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

Curb inlet in San Diego, an opening in the curb face beside the gutter, with a round lid in the slab above

"Curb inlet and catch basin" by Mds08011 — https://commons.wikimedia.org/wiki/File:Curb_inlet_and_catch_basin.jpg — CC BY 4.0 (https://creativecommons.org/licenses/by/4.0/)

The drawing is a schematic street section of a combined system, with one pipe for wastewater and rainwater; the photograph is a curb inlet and catch basin in San Diego, the street-level opening that both kinds of system have.

Basis Pipe roles follow the EPA's definition of a combined sewer system; positions are schematic and carry no depths.

Legend: letters and numbers on the drawing

  • A building connection
  • B curb inlet and catch basin
  • C manhole shaft
  • D water main
  • E combined sewer

Rainwater running along a curb drops through a slot or an iron grate and is gone. Where it goes next depends on the kind of system under that street. In a combined system, the U.S. Environmental Protection Agency explains, “both wastewater and stormwater flow through the same pipes.” In a separate system, the rain gets a set of pipes of its own.

Either way, the pipes run downhill wherever the ground allows. Where it does not, a pump can lift the flow.

Where does wastewater go first?

The trip from a sink to a river runs through a short chain of parts, and most of the chain is a pipe on a slope. The steps below follow the design chapters of the 2014 Recommended Standards for Wastewater Facilities, known as the Ten States Standards, and the EPA's description of sanitary sewers.

Schematic long section of a sewer line falling by gravity, lifted by a lift station, then falling again

Model schematic layout, not any city

Open the drawing full size

A schematic long section: gravity sewers fall from manhole to manhole, a lift station raises the flow into a pressure pipe, and gravity takes over again for the last run to the plant.

Basis Sequence follows Ten States Standards (2014 edition), chapter 30 on gravity sewers and chapter 40 on pumping stations; slopes are not to scale.

Legend: letters and numbers on the drawing

  • A gravity sewer
  • B manhole
  • C lift station (wet well and pump)
  • D force main, a pipe kept under pump pressure
  • E receiving manhole
  • F treatment plant

"Gravity sewers and a lift station, long section (schematic)" by Built, Mapped & Planted, https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/ — CC BY 4.0, https://creativecommons.org/licenses/by/4.0/

Data: Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

  1. A sink, toilet or floor drain empties into the building's own drain, which leaves the building as a building connection.
  2. The connection runs to the sewer in the street. The Ten States Standards say a sewer should in general lie deep enough to receive wastewater from basements and to stay clear of freezing (2014 edition, §33.2).
  3. Street sewers join larger sewers at manholes. The standard calls for a manhole at the end of each line, at every change in grade, size or direction, and at every intersection (§34.1).
  4. Between two manholes the pipe keeps one uniform slope (§33.44), so the flow keeps falling from one manhole to the next.
  5. Where the ground rises across the route, a pumping station lifts the flow, and gravity takes over again downstream (chapter 40).
  6. The last sewer delivers the flow to a wastewater treatment plant. In the EPA's words, the wastewater “is treated before being discharged to a waterbody.”

A pipe that falls steadily moves its flow without a pump. That is why, in this sequence, a pump appears only at the point where the slope runs out.

How far apart are manholes?

Manhole spacing is set by rule too. The Ten States Standards allow at most 400 feet between manholes on sewers of 15 inches or less and 500 feet on sewers of 18 to 30 inches, with up to 600 feet where modern cleaning equipment for that spacing is provided (2014 edition, §34.1). Where an incoming sewer enters a manhole 24 inches or more above the invert, the bottom of the flow channel, the standard calls for a drop pipe (§34.2).

What does a lift station do?

A lift station is the common name for what the Ten States Standards call a wastewater pumping station. Wastewater collects in a wet well, a chamber that the pumps draw from, and the pumps push it through a force main, a pipe under pressure, up to a higher point on the route. The standard lists four types in general use: wet well and dry well, submersible, suction lift and screw pump (2014 edition, §42.1).

The force main does not run all the way to the plant in this layout. The standard's design rules have it enter a receiving manhole with a smooth transition back to the gravity sewer system (§49.3). From that manhole, the flow is back on a slope.

Inside the force main, the standard asks for a cleansing velocity of at least 2 feet per second at design pumping rates and recommends no more than 8 feet per second, to avoid high head loss and protect valves. It sets the smallest force main for raw wastewater at 4 inches across (2014 edition, §49.1).

How steep does a sewer pipe have to be?

Not very steep at all. The Ten States Standards (2014 edition, §33.41) recommend a minimum slope of 0.40 ft per 100 ft for an 8-inch sewer, the smallest size the standard allows for a public gravity sewer carrying raw wastewater (§33.1). That works out to 4.8 inches of fall over a 100-ft run, or 0.4 percent.

Bar chart of Ten States minimum sewer slopes, falling from 0.40 to 0.037 ft per 100 ft as pipes get larger

Open the drawing full size

Recommended minimum slope for each nominal sewer size from 8 to 42 inches, in feet of fall per 100 feet of pipe.

Basis Minimum slopes from Ten States Standards (2014 edition, §33.41).

"Recommended minimum sewer slopes by pipe size" by Built, Mapped & Planted, https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/ — CC BY 4.0, https://creativecommons.org/licenses/by/4.0/

Data: Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

The standard sets these slopes so that a sewer flowing full moves at a mean velocity of at least 2.0 feet per second, calculated with Manning's formula and a roughness coefficient, n, of 0.013 (2014 edition, §33.41). Larger pipes reach that speed at flatter slopes, so the recommended minimum falls as the size rises, down to 0.037 ft per 100 ft for a 42-inch sewer.

The table is a set of recommended minimums from one regional standard. Its authors are the Great Lakes – Upper Mississippi River Board, whose members are ten U.S. states and the province of Ontario. The same section notes that steeper slopes may be wanted for construction, to control sewer gases, or to keep the flow fast enough to clean the pipe at all rates of flow.

Nominal sewer sizeMinimum slope, ft per 100 ft (Ten States, 2014)
8 in (200 mm)0.40
10 in (250 mm)0.28
12 in (300 mm)0.22
15 in (375 mm)0.15
18 in (450 mm)0.12
21 in (525 mm)0.10
24 in (600 mm)0.08
27 in (675 mm)0.067
30 in (750 mm)0.058
33 in (825 mm)0.052
36 in (900 mm)0.046
39 in (975 mm)0.041
42 in (1050 mm)0.037

Download the minimum-slope table (CSV) (where this data comes from) Data: Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

Can a sewer be too steep?

In the standard's terms, yes. Where velocities pass 10 feet per second, it asks for special provisions against scour and against pipes being displaced by erosion or impact (2014 edition, §33.45). Sewers on slopes of 20 percent or more must be anchored with concrete or equal anchors, set closer together as the grade steepens (§33.46).

The table also bends the other way. Slopes slightly flatter than the recommended minimum may be permitted where the flow will be at least 0.3 of the pipe diameter deep at the design average flow, provided the operator of the system gives written assurance of the extra maintenance the flatter pipe will need (§33.42).

Combined or separate?

In the EPA's description, a separate system has two sets of pipes: one carries wastewater from homes and businesses to a treatment plant, and the other collects stormwater from drains along streets, around parking lots and at the ends of driveways and carries it to a local waterway. A combined system uses one set for both. The EPA adds: “Most U.S. communities today have separate sanitary sewer systems.”

Schematic street section of a separate system, with a sanitary sewer and a storm sewer side by side

Model schematic layout, not any city

Open the drawing full size

The same schematic street with a separate system: building wastewater goes to a sanitary sewer, and the curb inlet feeds a storm sewer of its own.

Basis Pipe roles follow the EPA's description of separate sanitary sewer systems; positions are schematic and carry no depths.

Legend: letters and numbers on the drawing

  • A building connection
  • B curb inlet and catch basin
  • C manhole shaft
  • D water main
  • E sanitary sewer
  • F storm sewer

"Street section, separate sewer system (schematic)" by Built, Mapped & Planted, https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/ — CC BY 4.0, https://creativecommons.org/licenses/by/4.0/

Data: U.S. Environmental Protection Agency (EPA), Combined Sewer Overflow Basics (updated 2026-09-24), retrieved 2026-11-18; Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

Are storm drains connected to sewers?

In a separate system, not to the sanitary sewer: the curb inlet feeds a storm sewer that ends at open water, not at the treatment plant. In a combined system, the curb inlet and the toilet drain into the same pipe. For new work, the Ten States Standards say reviewing authorities will in general approve sanitary sewers only when they are designed on the separate basis, with rainwater from roofs and streets and groundwater from foundation drains kept out (2014 edition, §31).

The water main in both drawings belongs to the supply side, the pipe that brings drinking water in; water towers show how height pushes that water through the mains. The Ten States Standards call for sewers to be laid at least 10 feet horizontally from any water main, measured edge to edge (§38.31). The drawings are not to scale and do not show that distance.

Layer by layer, from the street surface down, the two layouts compare like this.

Layer in this layoutCombined systemSeparate system
Curb inlet and catch basindrains to the combined sewerdrains to the storm sewer
Building connectiondrains to the combined sewerdrains to the sanitary sewer
Water mainsupply side, apart from the sewersupply side, apart from the sewers
Manhole shaftreaches the combined sewerreaches the sanitary sewer
Sewer pipesone pipe for wastewater and stormwatersanitary sewer to the plant; storm sewer to a waterway

Download the layer list for both layouts (CSV) (where this data comes from) Data: U.S. Environmental Protection Agency (EPA), Combined Sewer Overflow Basics (updated 2026-09-24), retrieved 2026-11-18; Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition, Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, retrieved 2026-11-18

What happens in heavy rain?

A combined sewer carries rain as well as wastewater, and a hard storm can bring more than it holds. The EPA describes the sequence: in dry weather, all wastewater flows to the treatment plant; in wet weather, stormwater also enters the system, and “the combined flow of wastewater and stormwater can overwhelm the system.” Permitted outfalls placed throughout the system act as relief points, and they discharge untreated or partially treated stormwater and wastewater into nearby waterbodies.

Schematic combined sewer in dry and wet weather, overflowing through a relief point to a waterbody

Model schematic layout, not any city; the relief opening is drawn above the dry-weather flow

Open the drawing full size

A schematic combined sewer in dry weather and in wet weather: when the combined flow is more than the system can carry, part of it leaves through a relief point to a nearby waterbody instead of reaching the plant.

Basis Follows the EPA's description of combined sewer overflows; no real outfall is drawn.

Legend: letters and numbers on the drawing

  • A combined sewer
  • B relief point, a permitted outfall in the EPA's description
  • C treatment plant
  • D nearby waterbody

"Combined sewer in dry and wet weather (schematic)" by Built, Mapped & Planted, https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/ — CC BY 4.0, https://creativecommons.org/licenses/by/4.0/

Data: U.S. Environmental Protection Agency (EPA), Combined Sewer Overflow Basics (updated 2026-09-24), retrieved 2026-11-18

Those discharges are combined sewer overflows, or CSOs. The EPA calls CSOs a major water pollution and public health concern for approximately 700 communities in the United States, as of its page update of September 24, 2026. The same page says CSOs can carry bacteria, debris and other hazardous substances, and it lists beach closures, shellfish bed closures, algae growth and reduced oxygen in waterways among their effects. It adds that the Clean Water Act requires communities with CSOs to put controls in place.

A count like this can change from one page update to the next, so it is given here with its date. One city's sewer, built inside a new river wall, is the subject of the Great Stink.

The drawings on this page reduce sewers to circles. Nadar's photograph, titled Carrefour de collecteurs, shows the scale they stand for: a vaulted crossing of large collector sewers under Paris in 1861.

Nadar's 1861 photograph of a vaulted junction of collector sewers under Paris, with pipes along the vault

Nadar's 1861 photograph of a junction of collector sewers under Paris, titled Carrefour de collecteurs, with pipes along the vault.

"Carrefour de collecteurs (Paris sewers), by Nadar" by Nadar — https://commons.wikimedia.org/wiki/File:Nadar,_Carrefour_de_collecteurs_(Paris_Sewers),_1861.jpg — Public Domain (US: listed as public domain by The J. Paul Getty Museum Open Content Program (object 84.XM.343.10), photographer d. 1910 (publication history not traced); EU: photographer died 1910, more than 70 years ago (life plus 70 years))

What you can see from the curb

The photograph at the top of the page puts the drawing's top layer at eye level: a gutter along the curb, an opening cut into the curb face, and a round lid in the concrete slab behind it. The file's description on Wikimedia Commons identifies a curb inlet and catch basin in San Diego, with a white stamp warning against dumping because the storm drain discharges to the ocean. A drain marked that way fits the EPA's picture of a separate storm sewer that ends at open water.

Close view of the San Diego curb inlet: the opening under the curb, a stamp on the curb top, a round lid

A closer view of the same San Diego inlet: the opening under the curb face, the stamp on the curb top and the round access lid in the slab behind it.

"Curb inlet and catch basin (detail)" by Mds08011 — https://commons.wikimedia.org/wiki/File:Curb_inlet_and_catch_basin.jpg — CC BY 4.0 (https://creativecommons.org/licenses/by/4.0/); modified: cropped to the curb opening, the stamp on the curb top and the lid in the slab

The round lid is an access cover for maintenance, not a viewing point. Covers are lifted, and shafts entered, only by trained crews following set procedures; the Ten States Standards also require confined-space entry equipment, under OSHA and agency rules, for every wastewater pumping station (2014 edition, §41.4). Everything else in this section can be read from the sidewalk.

Cite this page

Built, Mapped & Planted. “How Does a Sewer System Work? Sometimes Rain Shares the Pipe.” First issued 19 November 2026. https://builtmappedandplanted.com/infrastructure/how-a-sewer-system-works/. Accessed on the day you read it.

Sources

  1. U.S. Environmental Protection Agency, “Combined Sewer Overflow Basics,” National Pollutant Discharge Elimination System (NPDES), page last updated September 24, 2026. www.epa.gov/npdes/combined-sewer-overflow-bas…Read: full pageText license: U.S. Government work (17 U.S.C. §105) (terms)
  2. Great Lakes - Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, Recommended Standards for Wastewater Facilities (Ten States Standards), 2014 edition. www.health.mn.gov/communities/environment/water/doc…Read: chapter 30 (sections 31 to 38, including section 34 on manholes) and chapter 40 (sections 41, 42 and 49) read; figures quoted from the 2014 editionText license: 2014 edition: this document, or portions thereof, may be reproduced without permission if credit is given to the Board and to this publication as a source (terms)

How numbers and sources are checkedRedline sheet: all correctionsReport an error on this page (contact@builtmappedandplanted.com)

More sheets in Under the Street

Diagram deep-dive

Roman Aqueducts: By Frontinus’s Count, Mostly Underground

Picture credit

"Le Pont du Gard, by Hubert Robert" by Hubert Robert — https://commons.wikimedia.org/wiki/File:Le_pont_du_Gard_-_Hubert_Robert_-_Mus%C3%A9e_du_Louvre_Peintures_INV_7650.jpg — Public Domain (US: published before 1931; EU: artist died 1808, more than 70 years ago (life plus 70 years); faithful reproduction of a two-dimensional work)

Hubert Robert’s painting of the Pont du Gard, three tiers of stone arches over a river

Field sheet entry

Why Are Manhole Covers Round? Square Lids Can Fall In

Picture credit

"Manhole cover by Cavanagh Foundry Birr" by A.-K. D. — https://commons.wikimedia.org/wiki/File:Manhole_cover_by_Cavanagh_Foundry_Birr.jpg — CC0 1.0 (https://creativecommons.org/publicdomain/zero/1.0/)

Round manhole cover set in a paved surface in Kilkenny, its cast letters naming Cavanagh Foundry, Birr

Field sheet entry

How Water Towers Work: Pressure Comes From Height

Picture credit

"General view of the standpipe, with Pumping Station No. 1, from the HAER record of the Louisville Water Company Pumping Stations" by Jack Boucher and William G. Johnson, Historic American Engineering Record (HAER), National Park Service (NPS) — https://commons.wikimedia.org/wiki/File:General_view_of_the_standpipe,_with_Pumping_Station_No._1_to_the_left._-_Louisville_Water_Company_Pumping_Stations,_Zorn_Avenue_and_River_Road,_Louisville,_Jefferson_County,_KY_HAER_KY,56-LOUVI,72-7.tif — Public Domain (US: U.S. Government work (17 U.S.C. §105), Historic American Engineering Record (HAER) photograph, photographers listed as Jack Boucher and William G. Johnson; EU: no statutory public-domain basis; National Park Service (NPS) statement: "Materials created for HABS, HAER, or HALS are in the public domain."); modified: converted from TIFF to JPEG at full size

Louisville Water Company standpipe tower, a tall column on a base ringed by Corinthian columns, beside Pumping Station No. 1